TRADITIONAL PRODUCTS, ALREADY PRESENT IN PREVIOUS CATALOGS, COMPATIBLE WITH REFRIGERANTS BELONGING TO SAFETY GROUP A1 AS DEFINED IN ASHRAE STANDARD 34-2019.
Accessories for use with the following ASHRAE 34:2019 refrigerants, Class A1: HCFC (R22) HFC (R134a, R404A, R407C, R410A, R507) HFO (R1234ze) HFO + HFC (R448A, R449A, R450A, R452A, R513A, R515A, R515B)
These valves are only sold in the model without the coil (S suffix), with 9 nozzles assembled for an increasing output from 1 to 22 kW with R410A.
Product Details
Orifice type
07
Rated capacity (1) [kW] R134a
11,26
Rated capacity (1) [kW] R22
14,35
R23
21,4
R404A
10,51
R507
10,51
R407C
14,66
R410A
17,22
R1234ze
8,84
R448A
14,03
R449A
13,77
R450A
9,88
R452A
10,88
R513A
9,55
R515A
8,51
R515B
8,47
Package pcs.
180
Notes where expressly stated
(1) Rated capacities are based on: - Evaporating temperature Tevap = + 5 °C - Condensing temperature Tcond = + 32 °C - Refrigerant liquid temperature ahead of valve Tliq = + 28 °C
Rated capacities in R23 are based on: - Evaporating temperature Tevap = - 30 °C - Condensing temperature Tcond= - 4 °C - Refrigerant liquid temperature ahead of valve Tliq = - 8 °C